Shell-and-Tube Condensers

Shell-and-Tube Condensers

Water-cooled refrigerant condenser enquiries for chillers, process refrigeration and existing-equipment replacement. We review refrigerant service, total heat-rejection duty, circulating-water conditions, construction and maintainability.

Illustrative HVACR installation photograph, not EVAPNEX equipment

Illustrative photograph: Armchoir / Wikimedia Commons (public domain); not an EVAPNEX product.

Thermal duty and condenser-water conditions

The condenser must reject the evaporator cooling duty plus compressor heat input; nominal refrigeration tonnage alone does not define condenser duty. Confirm refrigerant, total heat rejection, condensing temperature/pressure, cooling-water entering/leaving temperatures, fluid flow and permitted pressure loss.

Applications and configurations

  • New water-cooled chiller and industrial refrigeration condenser packages.
  • Replacement condenser matching to an existing equipment schedule, nameplate and site connection arrangement.
  • Application-specific construction for process water, marine or corrosive conditions where confirmed available.
  • Condenser-water system review together with cooling towers, pumps and filtration.

Mechanical design and maintenance

Specify design pressures on refrigerant and water sides, tube/shell materials, fouling allowances, connection orientation, overall dimensions, drain/vent arrangements, service clearance and tube-cleaning access. Removable-bundle options, coatings and non-standard materials require manufacturer confirmation.

Quotation information

  • Condenser heat-rejection duty in kW, refrigerant and required condensing conditions.
  • Cooling-water fluid, temperatures, flow, water quality and fouling allowance.
  • Allowable hydraulic pressure losses and operating/design pressure ratings.
  • Existing unit photograph and nameplate, dimensions, nozzle arrangement and mounting details.
  • Required pressure-vessel code, test reports, inspection and project documentation.

Request a Quote →

Product availability, operating performance, dimensions, materials, approvals and documentation are confirmed against the selected manufacturer’s technical offer.