EVAPNEX supplies cooling-tower fill enquiries for original-brand and technically specified replacement applications. Use the product-family information below to identify the appropriate media for your existing tower, then share the duty, water quality, module dimensions and required quantity for a technical quotation.

Illustrative EVAPNEX category image. Individual manufacturer models differ in surface profile, sheet spacing and dimensions.
Brentwood AccuPac & AccuClean – Model Reference Table
The following figures come from the linked Brentwood six-page film-fill brochure hosted by Star Cooling Towers (copyright 2011). They describe the brochure’s product variants; confirm current model status, performance curves, available pack sizes and material against the manufacturer’s latest documentation before ordering.
| Brentwood model / family | Published surface area | Sheet spacing | Primary application |
|---|---|---|---|
| AccuPac CF1200 / CF1200MA | 226 m²/m³ | 11.7 mm | Compact cross-fluted fill for packaged counterflow towers; CF1200 may also be specified for distribution-pad duty. |
| AccuPac CF1900 / CF1900MA | 157.5 m²/m³ | 19 mm | Cross-fluted counterflow fill for HVAC and industrial cooling towers; review water cleanliness and thermal duty. |
| AccuPac CFS3000 | 102 m²/m³ | 30.5 mm | Larger channels for applications requiring more tolerance to fouling. |
| AccuPac OF21MA | 147.8 m²/m³ | 20.8 mm | Offset-vertical fill where fouling potential and heat transfer must be balanced. |
| AccuPac VF19PLUS | 154 m²/m³ | 19 mm | Vertical-flow fill for poorer water quality and elevated fouling risk. |
| AccuPac VF3800 | 131 m²/m³ | 38 mm | Larger vertical passages for more severe fouling conditions. |
| AccuClean AFVF19 / AFVF19MA | 138 / 144 m²/m³ | 19.4 / 19 mm | Anti-fouling vertical-flow fill; compare pack size and assembly version. |
| AccuPac XF125 | 210 m²/m³ | 12.5 mm | Crossflow media for packaged tower arrangements, subject to suitable water quality. |
| AccuPac XF75 / XF75IL / XF75ID | 167.4 m²/m³ | 19 mm | Crossflow herringbone fill; IL and ID are integrated-louver and integrated-eliminator components. |
| AccuPac CF1900SS | 157.5 m²/m³ | 19 mm | Stainless-steel fill enquiry for specific critical or high-temperature applications. |
Typical Pack and Material Information
- CF1900 brochure listing: 305 mm minimum depth, 153 mm minimum width and 305 mm minimum length; illustrated standard modules include 610 mm depth × 610 mm width × 3,658 mm length. Confirm production cut-to-size and shipping limits when quoting.
- CF1200 brochure listing: 100 mm distribution-pad minimum depth applies to CF1200, while CF1200MA specifies a minimum 300 mm depth. Other dimensions and mechanical-assembly options are variant dependent.
- XF75 crossflow product family: XF75IL denotes the inlet-louver fill section; XF75ID denotes the drift-eliminator fill section. Clarify whether the requirement is media alone or a complete integrated assembly.
- The brochure identifies PVC and a selection of other polymer options; stainless steel is specifically identified for CF1900SS. Confirm any high-temperature, fire-test, water-chemistry or material requirement for the quoted grade.
- Surface area and sheet spacing do not establish guaranteed tower capacity. Obtain appropriate KaV/L and air-pressure-drop selection data at the project’s water/air loading and wet-bulb conditions.
Published dimensions, material and configuration are manufacturer literature information, not confirmed stock or a universal replacement fit.
What to Send for a Fill Quotation
- Required manufacturer/model, or existing fill photographs and sheet/profile identification.
- Cell length, width and fill depth; support type and whether integral louvers and eliminators are needed.
- Water flow, hot/cold temperatures, wet-bulb design temperature and available fan static pressure.
- Water analysis and fouling/scaling history; maximum circulating-water temperature.
- Material or fire-standard requirement, delivery country and required quantity.